A new islanding detection technique based on passive parameter using artificial neural network evolutionary programing / Aimie Nadia Ab Salam

One of the main requirements of distribution utility companies related to interconnection of distributed generation (DG) is islanding detection technique. Islanding occurs when part of the distribution system becomes electrically isolated from the main supply, and it remains energized by DG in an is...

Full description

Saved in:
Bibliographic Details
Main Author: Ab Salam, Aimie Nadia
Format: Thesis
Language:English
Published: 2019
Online Access:https://ir.uitm.edu.my/id/eprint/84239/1/84239.pdf
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:One of the main requirements of distribution utility companies related to interconnection of distributed generation (DG) is islanding detection technique. Islanding occurs when part of the distribution system becomes electrically isolated from the main supply, and it remains energized by DG in an isolated subsystem. Failure to detect islanding may lead to power quality issues, equipment damage and safety issues concerning the electrical company workers. Therefore, DG connection codes worldwide require that all islanded DGs to be disconnected as fast as possible after the formation of islanding. Among islanding detection technique, computational intelligence technique is the most recent approach that can produce almost zero nondetection zone. The objective of this thesis is to design a new islanding detection technique for synchronous type of DG based on the most sensitive passive parameters by using Artificial Neural Network (ANN) Evolutionary Programming (EP). The most sensitive parameter is selected from the sixteen parameters designated for this study considering the sensitivity analysis. The analysis is produced based on the response of each parameter when the test system is subjected with different types of islanding and non-islanding event.