Performance Study Of Energy Recovery System With Two Different Sizes Of Heat Exchanger Under Hot-Humid Environment

This thesis reports the theoretical and experimental analysis of energy recovery system with two different sizes of heat exchangers under hot-humid environment. The heat exchangers were made of membrane based material with cross-flow arrangement with an ability to transfer both sensible and laten...

全面介紹

Saved in:
書目詳細資料
主要作者: Abul Rahman, Siti Masitah
格式: Thesis
語言:English
出版: 2018
主題:
在線閱讀:http://eprints.usm.my/60945/1/Performance%20study%20of%20energy%20cut.pdf
標簽: 添加標簽
沒有標簽, 成為第一個標記此記錄!
實物特徵
總結:This thesis reports the theoretical and experimental analysis of energy recovery system with two different sizes of heat exchangers under hot-humid environment. The heat exchangers were made of membrane based material with cross-flow arrangement with an ability to transfer both sensible and latent heat from hot-humid intake airstream. The two different sizes heat exchangers i.e. smaller size and bigger size were compared with theoretical and experimental analysis. In the theoretical and experimental analysis, Number of Transfer Unit-effectiveness method and ASHRAE standard method were used. The performance of the heat exchangers was analysed based on the operating parameters namely air velocity, intake temperature, relative humidity and recovered energy. The results showed that as the air velocity increased, the effectiveness of energy recovery system decreased.