Investigation of voltage sag problem on sensitive load using ride through simulation based mitigation equipment / Azura Samrek

This report focused on voltage sag happened to industrial consumer, which Compressor proven as sensitive equipment because the load affected when voltage sag event occurred. The Ride Through Simulation tested on the 2 points at the Compressor; Control Circuit and Starter Circuit. Compressor is main...

Full description

Saved in:
Bibliographic Details
Main Author: Samrek, Azura
Format: Thesis
Language:English
Published: 2013
Subjects:
Online Access:https://ir.uitm.edu.my/id/eprint/77921/1/77921.pdf
Tags: Add Tag
No Tags, Be the first to tag this record!