Improvement of the SAG ampacity carrying level of existing 275 kV overhead line tower by using the re-conductoring approach

This project presents a methodological approach, suggestions and information in uprating the existing 275kV transmission overhead line by using the re-conductoring approach. Overhead transmission line conductors were given priority in information. Calculation regarding the maximum sag and maximum...

Full description

Saved in:
Bibliographic Details
Main Author: Mahmod, Luqman Hakim
Format: Thesis
Language:English
English
English
Published: 2012
Subjects:
Online Access:http://eprints.uthm.edu.my/2272/1/24p%20LUQMAN%20HAKIM%20MAHMOD.pdf
http://eprints.uthm.edu.my/2272/2/LUQMAN%20HAKIM%20MAHMOD%20COPYRIGHT%20DECLARATION.pdf
http://eprints.uthm.edu.my/2272/3/LUQMAN%20HAKIM%20MAHMOD%20WATERMARK.pdf
Tags: Add Tag
No Tags, Be the first to tag this record!
id my-uthm-ep.2272
record_format uketd_dc
spelling my-uthm-ep.22722021-10-31T05:03:15Z Improvement of the SAG ampacity carrying level of existing 275 kV overhead line tower by using the re-conductoring approach 2012-07 Mahmod, Luqman Hakim TK Electrical engineering. Electronics Nuclear engineering TK1001-1841 Production of electric energy or power. Powerplants. Central stations This project presents a methodological approach, suggestions and information in uprating the existing 275kV transmission overhead line by using the re-conductoring approach. Overhead transmission line conductors were given priority in information. Calculation regarding the maximum sag and maximum current at maximum operating temperature were the core of this project as to suggest a novel conductor available in the current market. The aim of this project is to provide more current and less sag with the new conductor proposed in comparison with the existing. In addition, the conductor will not in any way infringe the minimum safety clearance. Smart Draw, Matlab and Excel were used as a medium in the data analysis. Therefore, the apparent power of the overhead transmission line when applied with the new conductor can be calculated as to achieve the objective of this project. In Malaysia, ACSR Zebra is used as the conductor for the 275 kV L3 tower. Thus, four other conductors were chosen in order to make comparison between the maximum sag and current at maximum operating temperature. These conductors are the 3M Drake, AAC Narcissus, AAAC Greeley and ACCC 415 mm2 which have similar characteristics to the ACSR Zebra in terms of weight, maximum rated strength ratio and size. By using the calculations provided in this project, it is determined that the 3M Drake conductor is better to the ACSR Zebra in comparison of the maximum sag and the curent at maximum opertaing temperature. 2012-07 Thesis http://eprints.uthm.edu.my/2272/ http://eprints.uthm.edu.my/2272/1/24p%20LUQMAN%20HAKIM%20MAHMOD.pdf text en public http://eprints.uthm.edu.my/2272/2/LUQMAN%20HAKIM%20MAHMOD%20COPYRIGHT%20DECLARATION.pdf text en staffonly http://eprints.uthm.edu.my/2272/3/LUQMAN%20HAKIM%20MAHMOD%20WATERMARK.pdf text en validuser mphil masters Universiti Tun Hussein Onn Malaysia Fakulti Kejuruteraan Elektrik dan Elektronik
institution Universiti Tun Hussein Onn Malaysia
collection UTHM Institutional Repository
language English
English
English
topic TK Electrical engineering
Electronics Nuclear engineering
TK Electrical engineering
Electronics Nuclear engineering
spellingShingle TK Electrical engineering
Electronics Nuclear engineering
TK Electrical engineering
Electronics Nuclear engineering
Mahmod, Luqman Hakim
Improvement of the SAG ampacity carrying level of existing 275 kV overhead line tower by using the re-conductoring approach
description This project presents a methodological approach, suggestions and information in uprating the existing 275kV transmission overhead line by using the re-conductoring approach. Overhead transmission line conductors were given priority in information. Calculation regarding the maximum sag and maximum current at maximum operating temperature were the core of this project as to suggest a novel conductor available in the current market. The aim of this project is to provide more current and less sag with the new conductor proposed in comparison with the existing. In addition, the conductor will not in any way infringe the minimum safety clearance. Smart Draw, Matlab and Excel were used as a medium in the data analysis. Therefore, the apparent power of the overhead transmission line when applied with the new conductor can be calculated as to achieve the objective of this project. In Malaysia, ACSR Zebra is used as the conductor for the 275 kV L3 tower. Thus, four other conductors were chosen in order to make comparison between the maximum sag and current at maximum operating temperature. These conductors are the 3M Drake, AAC Narcissus, AAAC Greeley and ACCC 415 mm2 which have similar characteristics to the ACSR Zebra in terms of weight, maximum rated strength ratio and size. By using the calculations provided in this project, it is determined that the 3M Drake conductor is better to the ACSR Zebra in comparison of the maximum sag and the curent at maximum opertaing temperature.
format Thesis
qualification_name Master of Philosophy (M.Phil.)
qualification_level Master's degree
author Mahmod, Luqman Hakim
author_facet Mahmod, Luqman Hakim
author_sort Mahmod, Luqman Hakim
title Improvement of the SAG ampacity carrying level of existing 275 kV overhead line tower by using the re-conductoring approach
title_short Improvement of the SAG ampacity carrying level of existing 275 kV overhead line tower by using the re-conductoring approach
title_full Improvement of the SAG ampacity carrying level of existing 275 kV overhead line tower by using the re-conductoring approach
title_fullStr Improvement of the SAG ampacity carrying level of existing 275 kV overhead line tower by using the re-conductoring approach
title_full_unstemmed Improvement of the SAG ampacity carrying level of existing 275 kV overhead line tower by using the re-conductoring approach
title_sort improvement of the sag ampacity carrying level of existing 275 kv overhead line tower by using the re-conductoring approach
granting_institution Universiti Tun Hussein Onn Malaysia
granting_department Fakulti Kejuruteraan Elektrik dan Elektronik